Guide · Faults

Solar pump controller error codes, explained

Codes and lights from the manuals of Lorentz PS2, Grundfos CU 200, Veichi SI23 and ZRI controllers, in tables, with what is safe to check yourself and when to call a technician.

Updated 28 Nov 2026 · 9 min read By Peter Kamau
A technician wiring solar panels
On this pageLorentz PS2Grundfos CU 200 (SQFlex)Veichi SI23 solar pump inverterGeneric controllers (ZRI)Doyin and other controllersWhat to do with a code
The short answer

Codes are not universal: the same letters mean different things on different brands. Find your controller's brand and model, then read its table below. We list what the published manuals of Lorentz PS2, Grundfos CU 200, Veichi SI23 and ZRI say, and cite each manual. We found no published fault list for Doyin controllers.

A code on the screen is the controller telling you why it stopped the pump. Most of the time it is protecting the pump, and the fix is outside the controller: more sun, more water, a clear pipe, a cable. Start with nine checks when a pump is not pumping water. If you need someone to look, see solar pump repair. To compare controllers, look at the controllers category, and to check your pump matches the load, use the sizing calculator. More on the guides page.

Read this first. Codes depend on the brand. The tables below come from published manuals and are quoted in short. Your model may use different codes. Do not open the controller: panels send voltage to it whenever there is light, and Grundfos says fault finding must be done by qualified persons.

Lorentz PS2

The Lorentz PS2 range is sold in Kenya (see the Lorentz PS2-600 fiche). Its controller reports a “pump off reason” in the PumpScanner phone app. The Lorentz Australia distributor guide lists these (Table 3). We keep the manual’s wording close; the right-hand column is the action it gives.

Pump off reason What it means Action in the guide
Source Low Sensor detected a low water source. Pump restarts 15 minutes after water is registered again Check for a broken sensor, wait for the source to recover
Remote Switch Remote switch sensor triggered. Restarts 15 minutes after it resets Check for a broken sensor, check the storage is full
Water Sensor Water sensor detected an event Check for a low source, or an air leak in the pipe
Overload Controller detected an overload and stopped the motor. Many causes, a pump inspection may be required Toggle the on/off switch to reset, inspect the system, check for dirt build-up or a seized rotor/stator
Overvoltage Overvoltage limit exceeded, controller will not start The panel array needs to be reconfigured to spec
Manual software switch off Stopped in the app Check Pump Speed in Operational Settings
Sun Sensor Irradiation below the minimum setting Change in installation settings
Pressure / Liquid Level Sensor Stopped for high or low pressure, starts when pressure is back in range Change in Feature Settings
Daily Amount Set daily pumping amount reached, restarts next day Change in Feature Settings
Battery Low (LVD) Input voltage low, pump stopped to protect the battery Restarts when recovered
Timer Stopped by a software setting Change in Operation Settings
Min. Speed Minimum motor speed to run the pump cannot be reached Wait for more sun, or change in Operational Settings
Analog Input 1 or 2 error Controller gets implausible readings from a sensor (valid range 4 to 20 mA) Check sensor connection and polarity, replace the sensor if faulty
Over-temperature Controller too hot, power reduced or pump stopped, usually poor ventilation Restarts when cooled, improve ventilation
Sun Sensor Fault Implausible readings from the sun sensor module Check connection and polarity, replace the sensor
Internal Comm Error (Bt) or (mppt) Main board has to be replaced Normally replace the entire controller
Low Power Stopped for low power, likely morning, evening or sudden clouds If sufficient light, go through power checks
Short Circuit Motor Cable High current peak detected, motor stopped to protect the controller Inspect the system, check the motor cable especially
Internal Comm Error (LED) Problem with the LED board Check LED board wiring, if fine replace the LED board

The same guide gives a table of voltages for the PS2 range. For a PS2-600, the minimum voltage at maximum power point for full speed is 68 V DC and the maximum is 150 V DC.

Grundfos CU 200 (SQFlex)

The Grundfos service instructions for SQFlex describe the CU 200 control unit’s lights and codes. When the red fault light is on, the display shows a code.

Light or code Meaning in the manual
Green running light Pump is running at more than 500 rpm
Yellow light Water reservoir is full
Green light on the on/off button System switched on
Red light on the on/off button System switched off
Both lights off System lacks the power to light the display
Flashing green light Enough power for the display, not enough to start the pump
Red fault light with “dry running” mark Lack of water
F1 Overvoltage
F2 Overtemperature
F3 No contact to the pump
F4 Overload

What the manual lists as causes and remedies:

Code Possible causes Remedy in the manual
F1 overvoltage Supply voltage above the permitted range Disconnect the solar modules to let the voltage drop, then reconfigure the modules and reconnect. Allow for voltage drop in the pump cable
F2 overtemperature Water too hot, scale (incrustations) on the motor, defective pump Make sure water temperature is below the permitted maximum, remove scale from the motor, repair or replace the pump
F3 no contact to pump Defective CU 200, defective pump cable or connections, defective pump Check the connection in the CU 200, the pump cable and the end cover with socket on the pump. Repair or replace the pump
F4 overload Input voltage too low, defective pump, helical rotor pump with oily water, low or missing motor liquid Raise the supply voltage to 30 V DC or more, clean the liquid and replace the pump, check or refill motor liquid, repair or replace the pump

Other lines in the manual: a flashing green light with an insufficient power supply means add modules or another energy source, or the pump has seized up and needs cleaning. A running light with low wattage can mean the system is not grounded or the pump is defective. A pump that does not stop with a full reservoir can have a dirty or defective level switch, a damaged level switch cable, or a defective CU 200.

Veichi SI23 solar pump inverter

Veichi inverters are sold in Kenya (see the Veichi fiche). Our listing does not say which Veichi series it is, so check the label before relying on the SI23 manual. The SI23 manual separates alarms (the pump pauses and retries) from faults (the drive trips). Chapter 4 lists these alarms:

Display Alarm Reason in the manual What it says to check
A.LPn Dormancy protection Solar voltage is too low Check the solar power and parameters F21.11 to F21.13
AL.Fr Low frequency protection Output frequency too low, solar power not enough Check the solar power and parameters F21.14 to F21.16
A.LuT Dry run protection Current very low, pump load very low, not enough water in the borehole Check the water level in the borehole and parameters F21.17 to F21.19
AO.ld Pump over current protection Current higher than the set value Check the pump load and parameters F21.20 to F21.22
AL.Pr Minimum power protection Output power very low Check the solar power and parameters F21.23 to F21.25
AF.uL Water full protection Water tank is full Check the water tank and parameters F21.27 and F21.28
Clear Pump cleaning Pump cleaning process None

Faults in the same chapter include: E.LU2 (under-voltage while running), E.oU1 to E.oU4 (over-voltage), E.oC1 to E.oC3 (over-current), E.oL1 (motor overload), E.oL2 (drive overload), E.SC (short circuit of the output, or a phase short to ground), E.oH1 and E.oH2 (inverter and rectifier over-heat), E.TE1 and E.TE2 (motor detection fault), Ei.LF (input phase loss), Eo.LF (output phase loss), E.Gnd (output earth short), E.HAL (current detection fault) and EE.EP (memory fault). For over-current and short-circuit codes the manual points to the output wiring, the motor and the setup, which is work for a technician.

Generic controllers (ZRI)

Searches for “P0”, “PL” and “P51” lead to controllers sold under many names. ZRI publishes a table that uses those codes. We could not confirm that ZRI controllers are sold in Kenya, and we found no Difful manual, so use this table only if your controller is a ZRI.

Code Meaning Published cause or action
P0 Hardware over-current Short in the output, driver module error, or start on a spinning motor. If it stays with the motor wires removed, the controller hardware may be damaged
PL Low voltage or power low Input voltage too low, or panels poorly matched
P51 High voltage Input voltage too high, restore to the normal range
P1 Backwater protection Water flowing back through the pump
P44 Start-up failure Foreign objects in the impeller or an abnormal motor load
P48 Dry running or load drop Air in the pump, or motor power below the dry-run threshold
P60 High temperature Controller above 85 °C, clears when it cools

Doyin and other controllers

We found no published fault-code list for the Doyin MPPT controllers sold in Kenya. If you own one, ask the seller for its manual before you need it. See the Doyin controller fiche.

What to do with a code

  1. Photograph the controller, its label and the display.
  2. Note the time of day and the weather.
  3. Check what the table says is outside the controller: sun, water, tank, pipes, cables.
  4. If the code points to over-current, a short circuit, a motor cable, an internal communication fault or a hardware fault, stop and call a technician. We pass your request to one EPRA-licensed installer and tell you who before sharing your details. Start from solar pump repair, or see how to install a pump properly.

Pumps that fit

Doyin · Controller MPPT controller, 600 W
600 WPower600 W (the model name on the listing)Rated power800 W (KSh 14,999) and 1,500 W (KSh 16,999), in search extracts onlyOther Doyin ratings seen
From KSh 11,999 Seen 28 Nov 2026 · Jiji (private listing, Nairobi Central)
Get a confirmed quote
Solartech (Sunverter) · Controller SV3 inverter, 1.5 kW
1,500 WPower1.5 kWRated powerMPPT up to 99%, conversion up to 98%Efficiency
From KSh 95,000 excl. VAT Seen 28 Nov 2026 · tdk.co.ke
Get a confirmed quote
Lorentz · DC 600 W Lorentz, 30 m, 6.5 m³/h
600 WPower30 mMax head6,500Flow L/h
From KSh 196,000 excl. VAT Seen 28 Nov 2026 · tdk.co.ke
Get a confirmed quote
Solar pump controllers and inverters

Sources

Questions about this

Do the same error codes mean the same thing on every solar pump controller?
No. P0 is a hardware over-current on the ZRI controller table below, but a Grundfos CU 200 uses F1 to F4, and Lorentz PS2 shows reasons such as Source Low or Overload in its phone app. Always use the manual for your exact brand and model.
My controller says dry run. What should I do?
Check the water level in the borehole first. The Veichi SI23 manual lists its dry-run alarm (A.LuT) as a very low pump load and not enough water in the borehole. The Grundfos CU 200 shows a red fault light for lack of water. Do not bridge the sensor. Find out why the water fell.
What does a low-voltage or low-power code mean?
The panels are not giving enough power. This is normal early and late in the day and under cloud. If it happens at midday with clean panels, a technician should check the panel strings and the wiring.
Where can I find the manual for my controller?
Look for the brand and model on the controller's label, then search the maker's website for 'manual' plus the model. Keep a photo of the label. If the seller cannot give you the manual, that is worth knowing before you buy.

Get a confirmed quote

Free and without obligation. We pass your request to one EPRA-licensed installer in your county, and tell you who before we share your details.

Common:
We need the county to find a licensed installer near you
What the water is for
Pick all that apply.
Please tick the box so we can pass on your request
No payment now. No spam calls.
What happens next
1We read your request and choose one EPRA-licensed installer who works in your county.
2We tell you who it is. Only then do we share your name, phone and county with them.
3The installer checks your borehole and sends a written, itemised quote. You decide.
Your data Used only to answer this request, under Kenya's Data Protection Act 2019. Never sold, never shared with more than one installer. Privacy policy
Size my pumpGet a quote