Lorentz PS2Grundfos CU 200 (SQFlex)Veichi SI23 solar pump inverterGeneric controllers (ZRI)Doyin and other controllersWhat to do with a codeCodes are not universal: the same letters mean different things on different brands. Find your controller's brand and model, then read its table below. We list what the published manuals of Lorentz PS2, Grundfos CU 200, Veichi SI23 and ZRI say, and cite each manual. We found no published fault list for Doyin controllers.
A code on the screen is the controller telling you why it stopped the pump. Most of the time it is protecting the pump, and the fix is outside the controller: more sun, more water, a clear pipe, a cable. Start with nine checks when a pump is not pumping water. If you need someone to look, see solar pump repair. To compare controllers, look at the controllers category, and to check your pump matches the load, use the sizing calculator. More on the guides page.
Read this first. Codes depend on the brand. The tables below come from published manuals and are quoted in short. Your model may use different codes. Do not open the controller: panels send voltage to it whenever there is light, and Grundfos says fault finding must be done by qualified persons.
Lorentz PS2
The Lorentz PS2 range is sold in Kenya (see the Lorentz PS2-600 fiche). Its controller reports a “pump off reason” in the PumpScanner phone app. The Lorentz Australia distributor guide lists these (Table 3). We keep the manual’s wording close; the right-hand column is the action it gives.
| Pump off reason | What it means | Action in the guide |
|---|---|---|
| Source Low | Sensor detected a low water source. Pump restarts 15 minutes after water is registered again | Check for a broken sensor, wait for the source to recover |
| Remote Switch | Remote switch sensor triggered. Restarts 15 minutes after it resets | Check for a broken sensor, check the storage is full |
| Water Sensor | Water sensor detected an event | Check for a low source, or an air leak in the pipe |
| Overload | Controller detected an overload and stopped the motor. Many causes, a pump inspection may be required | Toggle the on/off switch to reset, inspect the system, check for dirt build-up or a seized rotor/stator |
| Overvoltage | Overvoltage limit exceeded, controller will not start | The panel array needs to be reconfigured to spec |
| Manual software switch off | Stopped in the app | Check Pump Speed in Operational Settings |
| Sun Sensor | Irradiation below the minimum setting | Change in installation settings |
| Pressure / Liquid Level Sensor | Stopped for high or low pressure, starts when pressure is back in range | Change in Feature Settings |
| Daily Amount | Set daily pumping amount reached, restarts next day | Change in Feature Settings |
| Battery Low (LVD) | Input voltage low, pump stopped to protect the battery | Restarts when recovered |
| Timer | Stopped by a software setting | Change in Operation Settings |
| Min. Speed | Minimum motor speed to run the pump cannot be reached | Wait for more sun, or change in Operational Settings |
| Analog Input 1 or 2 error | Controller gets implausible readings from a sensor (valid range 4 to 20 mA) | Check sensor connection and polarity, replace the sensor if faulty |
| Over-temperature | Controller too hot, power reduced or pump stopped, usually poor ventilation | Restarts when cooled, improve ventilation |
| Sun Sensor Fault | Implausible readings from the sun sensor module | Check connection and polarity, replace the sensor |
| Internal Comm Error (Bt) or (mppt) | Main board has to be replaced | Normally replace the entire controller |
| Low Power | Stopped for low power, likely morning, evening or sudden clouds | If sufficient light, go through power checks |
| Short Circuit Motor Cable | High current peak detected, motor stopped to protect the controller | Inspect the system, check the motor cable especially |
| Internal Comm Error (LED) | Problem with the LED board | Check LED board wiring, if fine replace the LED board |
The same guide gives a table of voltages for the PS2 range. For a PS2-600, the minimum voltage at maximum power point for full speed is 68 V DC and the maximum is 150 V DC.
Grundfos CU 200 (SQFlex)
The Grundfos service instructions for SQFlex describe the CU 200 control unit’s lights and codes. When the red fault light is on, the display shows a code.
| Light or code | Meaning in the manual |
|---|---|
| Green running light | Pump is running at more than 500 rpm |
| Yellow light | Water reservoir is full |
| Green light on the on/off button | System switched on |
| Red light on the on/off button | System switched off |
| Both lights off | System lacks the power to light the display |
| Flashing green light | Enough power for the display, not enough to start the pump |
| Red fault light with “dry running” mark | Lack of water |
| F1 | Overvoltage |
| F2 | Overtemperature |
| F3 | No contact to the pump |
| F4 | Overload |
What the manual lists as causes and remedies:
| Code | Possible causes | Remedy in the manual |
|---|---|---|
| F1 overvoltage | Supply voltage above the permitted range | Disconnect the solar modules to let the voltage drop, then reconfigure the modules and reconnect. Allow for voltage drop in the pump cable |
| F2 overtemperature | Water too hot, scale (incrustations) on the motor, defective pump | Make sure water temperature is below the permitted maximum, remove scale from the motor, repair or replace the pump |
| F3 no contact to pump | Defective CU 200, defective pump cable or connections, defective pump | Check the connection in the CU 200, the pump cable and the end cover with socket on the pump. Repair or replace the pump |
| F4 overload | Input voltage too low, defective pump, helical rotor pump with oily water, low or missing motor liquid | Raise the supply voltage to 30 V DC or more, clean the liquid and replace the pump, check or refill motor liquid, repair or replace the pump |
Other lines in the manual: a flashing green light with an insufficient power supply means add modules or another energy source, or the pump has seized up and needs cleaning. A running light with low wattage can mean the system is not grounded or the pump is defective. A pump that does not stop with a full reservoir can have a dirty or defective level switch, a damaged level switch cable, or a defective CU 200.
Veichi SI23 solar pump inverter
Veichi inverters are sold in Kenya (see the Veichi fiche). Our listing does not say which Veichi series it is, so check the label before relying on the SI23 manual. The SI23 manual separates alarms (the pump pauses and retries) from faults (the drive trips). Chapter 4 lists these alarms:
| Display | Alarm | Reason in the manual | What it says to check |
|---|---|---|---|
| A.LPn | Dormancy protection | Solar voltage is too low | Check the solar power and parameters F21.11 to F21.13 |
| AL.Fr | Low frequency protection | Output frequency too low, solar power not enough | Check the solar power and parameters F21.14 to F21.16 |
| A.LuT | Dry run protection | Current very low, pump load very low, not enough water in the borehole | Check the water level in the borehole and parameters F21.17 to F21.19 |
| AO.ld | Pump over current protection | Current higher than the set value | Check the pump load and parameters F21.20 to F21.22 |
| AL.Pr | Minimum power protection | Output power very low | Check the solar power and parameters F21.23 to F21.25 |
| AF.uL | Water full protection | Water tank is full | Check the water tank and parameters F21.27 and F21.28 |
| Clear | Pump cleaning | Pump cleaning process | None |
Faults in the same chapter include: E.LU2 (under-voltage while running), E.oU1 to E.oU4 (over-voltage), E.oC1 to E.oC3 (over-current), E.oL1 (motor overload), E.oL2 (drive overload), E.SC (short circuit of the output, or a phase short to ground), E.oH1 and E.oH2 (inverter and rectifier over-heat), E.TE1 and E.TE2 (motor detection fault), Ei.LF (input phase loss), Eo.LF (output phase loss), E.Gnd (output earth short), E.HAL (current detection fault) and EE.EP (memory fault). For over-current and short-circuit codes the manual points to the output wiring, the motor and the setup, which is work for a technician.
Generic controllers (ZRI)
Searches for “P0”, “PL” and “P51” lead to controllers sold under many names. ZRI publishes a table that uses those codes. We could not confirm that ZRI controllers are sold in Kenya, and we found no Difful manual, so use this table only if your controller is a ZRI.
| Code | Meaning | Published cause or action |
|---|---|---|
| P0 | Hardware over-current | Short in the output, driver module error, or start on a spinning motor. If it stays with the motor wires removed, the controller hardware may be damaged |
| PL | Low voltage or power low | Input voltage too low, or panels poorly matched |
| P51 | High voltage | Input voltage too high, restore to the normal range |
| P1 | Backwater protection | Water flowing back through the pump |
| P44 | Start-up failure | Foreign objects in the impeller or an abnormal motor load |
| P48 | Dry running or load drop | Air in the pump, or motor power below the dry-run threshold |
| P60 | High temperature | Controller above 85 °C, clears when it cools |
Doyin and other controllers
We found no published fault-code list for the Doyin MPPT controllers sold in Kenya. If you own one, ask the seller for its manual before you need it. See the Doyin controller fiche.
What to do with a code
- Photograph the controller, its label and the display.
- Note the time of day and the weather.
- Check what the table says is outside the controller: sun, water, tank, pipes, cables.
- If the code points to over-current, a short circuit, a motor cable, an internal communication fault or a hardware fault, stop and call a technician. We pass your request to one EPRA-licensed installer and tell you who before sharing your details. Start from solar pump repair, or see how to install a pump properly.
Pumps that fit
Sources
- Lorentz PS2, troubleshooting on-site (Lorentz Australia distributor guide, Table 3: pump-off reasons in PumpScanner)
- Grundfos, Service instructions: SQFlex water supply systems (CU 200 display, indicator lights, trouble-shooting by means of CU 200)
- Veichi, SI23 Solar Pump Inverter Manual, Chapter 4: fault diagnosis and solution
- ZRI, solar pump controller support page (fault codes)
- Lorentz, S1 controller help: troubleshooting overview